The fundamental building block of a cleanroom ceiling grid system is the connection/suspension system. It is important to select the most appropriate system matching the ceiling grid performance and compatibility design requirements to your cleanroom. Gordon offers several system options that, when mated with our numerous extruded aluminum grid types, provide the greatest number of speciality application-based cleanroom ceiling systems available from a single source.
Unit of Measure
Items
WS Gel Seal Grid Systems

12 Feet (ft) Length Main Tee

WS Gel Seal Grid Systems

4 ft Feet (ft) Length Cross Tee

WS Gel Seal Grid Systems

2 ft Feet (ft) Length Cross Tee

WS Gel Seal Grid Systems

12 ft Feet (ft) Length Wall Angle

WS Gel Seal Grid Systems

12 ft Feet (ft) Length Perimeter Tee
Description N/A Main Tee N/A Cross Tee N/A Cross Tee N/A Wall Angle N/A Perimeter tee/notched 24" or 48" O.C.
Brands N/A Gordon
Grid Member Material N/A Aluminum
Grid Member Width N/A 2 in
Grid Member Finish N/A Clear Anodized Powder Coat White
Type N/A Main Tee N/A Cross Tee N/A Cross Tee N/A Wall Angle N/A Perimeter Tee/Notched
Threaded Rod Size N/A 1/4-20
Material N/A Aluminum Alloy 6063
Industry Standards/Certifications N/A FM Approved
Web Depth (A) N/A 2-1/32 in
Flange Width (B) N/A 2 in N/A 2 in N/A 2 in N/A 1-1/4 in N/A 2 in
Length N/A 12 ft N/A 4 ft N/A 2 ft N/A 12 ft N/A 12 ft
Weight Per Linear Feet N/A 0.85 lb N/A 0.85 lb N/A 0.85 lb N/A 0.54 lb N/A 0.85 lb
Pieces per Carton N/A 8 N/A 16 N/A 36 N/A 12 N/A 8
Linear Feet per Carton N/A 96 N/A 144 N/A 72 N/A 144 N/A 96
Hanger Spacing (Span) for Deflection Formula L/360 N/A 24 in48 in
Main Tee Spacing for Deflection Formula L/360 N/A 48 in
Maximum Point Load for Deflection Formula L/360 N/A 296 lb629 lb
Maximum Uniform Load per Linear Feet for Deflection Formula L/360 N/A 74 lb314.5 lb
Applied Load per Square Feet for Deflection Formula L/360 N/A 18.5 lb78.6 lb
Deflection at Mid-Span for Deflection Formula L/360 N/A 1/16 in1/8 in
Hanger Spacing (Span) for Deflection Formula L/180 N/A 48 in
Main Tee Spacing for Deflection Formula L/180 N/A 48 in
Maximum Point Load for Deflection Formula L/180 N/A 314 lb
Maximum Uniform Load per Linear Feet for Deflection Formula L/180 N/A 78.5 lb
Applied Load per Square Feet for Deflection Formula L/180 N/A 19.6 lb
Deflection at Mid-Span for Deflection Formula L/180 N/A 1/4 in
WS Components and Accessories N/A 2-Way Corner Connector 3-Way Connector 4-Way Connector Blank Panels DS-cross Tee Filter Modules Hold Down Clips Lights-Tear Drop Main Tee Splice Connector Perimeter Trim Rod/Turnbuckle Sprinkler Adapter Panel WS-20 Main Tee WS-20 Perimeter Angle WS-20 Perimeter Tee
Extrusions N/A Grid members shall be extruded of aluminum alloy 6063, with temper T5, and shall feature upturned flanges to create a channel to receive the filter sealant gel, and a continuous 1/4-20 screw boss for field attachment of connecting and suspending devices. Cross tees shall have ends which are factory back cut and coped for optimal face alignment and system strength.
Finish N/A Standard finishes are either clear anodized or white powder coat. Custom finishes are also available.
Light Fixture Compatibility N/A Teardrop fixtures: Gordon's WS systems are designed to mate perfectly with standard 2-inch teardrop light fixtures. For greatest ease of installation, consider the Gordon WS-ScrewSlot extrusion.
Custom WS Blank Panels N/A When required, Gordon can provide blank panels with downturned knife edges to mate with the WS grid gel channel. Corners are welded and sealed, and are finished to match the WS grid members.
Fire Protection N/A Fire sprinkler penetrations may be accomplished via nominal 6-inch x 24-inch sprinkler blank panels, clamped in place and having a hole for sprinkler pipe installation. Optional thru-grid sprinkler provision is available utilizing exclusive FlexHead fire sprinkler assemblies thru factory fabricated grid penetrations. These assemblies are F.M. approved, and feature 6-feet long flexible stainless steel supply pipe on a 24-inch long nipple with mounting brackets and factory-installed sprinkler head. N/A N/A N/A N/A
WS-ScrewSlot Grid N/A When utilizing in-room utility/process pipe racking or teardrop light fixtures with 2-inch grid, consider the WS-ScrewSlot or the fastest, simplest, and cleanest installation alternative. Featuring a 1/4-20 continuous screw boss in the room side surface of the main tee, the WS-ScrewSlot extrusion allows for fast easy attachment of fasteners, rack attachments or teardrop light fixtures. And no drilling is required, eliminating any potential leak path into the cleanroom from the pressure plenum, and making installation of lighting and accessories clean and simple. A vinyl trim insert provides an attractive, secure seal for mains where no attachments are installed. The insert may be removed, trimmed, or relocated as additional equipment is installed or relocated. Consider this laborsaving, value added solution when reviewing your unique cleanroom design requirements.
Additional Information N/A
  • All systems are non-progressive, and can be factory-fabricated to specified grid module sizes.
  • Standard grid members can be provided with either clear anodized or powder coat white finish.
Note N/A

Our Philosophy

Creative thinking may mean simply the realization that there’s no particular virtue in doing things the way they always have been done
~Rudolf Flesch

About Us

© 2018 Technical Equipment Sales. All Rights Reserved | Site created by Thomas Marketing Services