Brands |
N/A AAF Flanders® PharmaGel™ |
Filter Type |
N/A High Efficiency Particulate Air (HEPA) |
Filter Housing Material |
N/A Aluminum |
Housing Thickness |
N/A 0.063 in |
Industry Standards/Certifications |
N/A Class 100 |
Testing |
N/A
The module may be leak tested in place. Introducing aerosol through the service port in the housing is not recommended. The 7⁄16" diameter port is small and aerosol vapor may condense on the internal housing surfaces, eventually dripping down onto the filter pack, saturating the fiberglass medium. In the event an aerosol test is desired, the smoke should be introduced into the upstream ductwork at least 10 diameters away, or preferably into the fan intake. The access port may be used to check the contamination level of the supply air any time. The AAF Flanders PharmaGel™ module is available with an optional 1/2" pipe size aerosol dispersion device for applications requiring room side testing. |
Housing Installation |
N/A
|
Filter Installation |
N/A
Before installing HEPA filter cartridges, the system must be balanced, cleaned, blown down, and operational with prefilters in place. This will minimize the amount of particulate swept into the filter pack at startup.
|
Operation |
N/A
Once in position, the PharmaGel™ module may be balanced and tested.
|
Maintenance and Care |
N/A
The PharmaGel™ module needs little maintenance. When installed downstream of a bank of AAF Flanders prefilters (90% ASHRAE efficiency), this module should provide years of service. An annual check of airflow is recommended. When the filter throughput eventually declines to an unacceptable level due to particulate accumulation, the filter cartridge should be replaced with a new AAF Flanders mini-pleat type, pocket seal filter. |
Caution |
N/A When performing the Filter Installation, Operation, and Testing procedures, do not open the damper beyond 2 1/2 turns of the Damper adjustment Screw. Exceeding 2 1/2 turns could result in damage to the unit. Dampers are shipped in the fully closed position. Do not open with the supply air on. |
Note for Housing Installation |
N/A Flange is not designed to support ceiling. Grout flange flush with ceiling. |
Note for Filter Installation |
N/A Setting filters properly requires two people. Do not install filters with supply air on. Install filters - then turn on supply air. |
Note for Filter Operation |
N/A The butterfly damper is a trim device and not intended to induce a large pressure drop. |
Note |
N/A AAF Flanders® has a policy of continuous product research and improvement and reserves the right to change design and specifications without notice. |